Conductive Cloth Tape,Double Sided Copper Tape,Conductive Metal Tape,Copper Foil Tape Kunshan An De Qing Electric Technology Co., Ltd. , https://www.andeqing.com
Technical Specifications
Â
Temp Adjustment Range
30-50ºC
Cold Inlet Temperature RangeÂ
5-30ºC
Hot Inlet Temperature RangeÂ
55-100ºC
Max Working Pressure (static)Â
1400kPa
Minimum Dynamic PressureÂ
210kPa
Maximum Dynamic PressureÂ
600kPa
Max Unbalanced Supply PressureÂ
6:1
Minimum Flow RateÂ
8 l/min
Max Recommended Flow @ 150KPa DP
EME30 - eyewash unit
EMS90 - Â Combo unit
Â
30 l/min
90 l/min
Â
Advantage
Emergency Mixing System
           3.Cold shock fail safe featureÂ
           4.Hot temperature fluctuation stability feature.Â
           5.Cold temperature fluctuation stabilityÂ
           6.Quick react pressure featureÂ
           7.Unequal inlet pressures easily controlledÂ
           8.Drips from the valve will be less than 46°C,Â
           9.Dormant period restart safety feature      Â
Â
Application
Pressure Loss Chart
Fault Finding in Common
Â
Model NO.: TMV
Origin: Zhejiang, China
Description